Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding

Product Details
Customization: Available
Material: Aluminum
Usage: for Air Conditioner, for Manufacture
Gold Member Since 2011

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Export Year
2005-12-25
Import & Export Mode
Have Own Export License
Terms of Payment
LC, T/T, Western Union
  • Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding
  • Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding
  • Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding
  • Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding
  • Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding
  • Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding
Find Similar Products
  • Overview
  • Product Description
  • Design
  • Testing
  • Bird Mesh Screen
  • Packaging & Shipping
  • Project Reference
Overview

Basic Info.

Model NO.
Togen
Type
Square Diffuser
Venetian-Style Air Layers
Single
Installation
Outlet
Transport Package
Attach PE Film on The Surface of Aluminum Profile,
Specification
louver height: 1055mm
Trademark
Togen
Origin
China
HS Code
73089000
Production Capacity
4500 Meter/Meters Per Day

Product Description

 
Product Description

Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding

Vertical Double Bank Louver VDL150-3
 

Blade Pack Depth 145mm
Frame Depth 150mm
Pitch 75mm
Visual Impact Hidden
Free Area /

Rainwater Penetration
 
VENTILATION RATE WATER FLOW RATES Effectiveness Class
Volume
m³/s
Velocity
m/s
Supply
l/h
Penetrated
l/h
0.00 0.00 97.2 0 100% A
0.46 0.50 97.2 0 100% A
0.93 1.00 97.2 0 100% A
1.39 1.50 97.2 0 100% A
1.86 2.00 97.2 0 100% A
2.32 2.50 97.2 0 100% A
2.79 3.00 97.2 0 100% A
3.26 3.50 97.2 0 100% A

Coefficient of Entry
 
  loure face velocity air flow rate  
louver pd 
Pascals
m/s test
m³/s
theoretical
m³/s
coefficient
Ce
10.3 1.10 1.026 3.836 0.268
24.2 1.72 1.596 5.881 0.271
37.5 2.17 2.022 7.320 0.276
52.7 2.57 2.395 8.678 0.276
66.2 2.90 2.693 9.726 0.277
79.9 3.20 2.973 10.685 0.278
95.4 3.47 3.232 11.676 0.277
112.0 3.72 3.459 12.651 0.273
130.0 4.01 3.735 13.630 0.274
143.0 4.27 3.969 14.295 0.278
      mean Ce 0.275
      Class 3


Tested by BSRIA-EN-13030:2001Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding

 

Design

Design
Our performance louver systems are designed using airflow simulation by CFD(computational fluid dynamics)software to get the best balance between airflow and rain defense performance
Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding

 

Testing

Testing

Weather Louvre: UK BSRIA/US AMCA Testing

The industry standard for weather testing of Louver in the UK was developed by BSRIA(Building Services Research & Information Association) and HEVAC adopted in 2001 as a British & European Standard: BS EN 13030:2001. The principles of EN 13030 are replicated in the USA under the AMCA Standard 500-L, "Laboratory Methods of Testing Louvers for Rating"
All of our louver systems have been tested either by BSRIA or by AMCA
Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall CladdingTwo key performance areas:
1. Rain Defence Classification
The ability to prevent rainwater from penetrating the louver
Class  Effectiveness Max. allowed rain penetration l/h/m²
1 1 to 0.99 0.75
2 0.989 to 0.95 3.75
3 0.949 to 0.80 15.00
4 Below 0.80 Greater than 15.00
NOTE: Water Penetration Effectiveness is measured for each of eight face velocities between 0m/s and 3.5m/s under fan-driven wind at a speed of 13m/s and water sprayed as rainfall at a rate of 75 l/h conditions.
2. Discharge Loss Coefficient Classification
A high coefficient means low resistance and high airflow performance
Class Airflow Effectiveness Performance Rating
1 0.4 to 1 Excellent
2 0.3 to 0.399 Very Good
3 0.2 to 0.299 Good
4 0.199 & below Fair

If you are interested in our product or have any questions. Please feel free to contact us!

 
Bird Mesh Screen

 

Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding
Notes:
W--Width of the mesh
D--Diameter of the wire
 
Regular Size of Insect/Bird Mesh Screen(mm)
Mesh Width of the mesh Diameter of the wire
Insect Mesh Screen 1.5*1.5 0.25
2*2 0.5
2.5*2.5 0.5
Bird Mesh Screen 5*5 0.8
10*10 1,1.6
11.2*11.2 1.6
12.5*12.5 1.6
Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding
Notes:
S--SWD
L--LWD
T--Strand thickness
 
Bird Mesh Screen(Diamond)
Mesh Width of the mesh Stand thickness
Bird Mesh Screen(Diameter) 10*20 1,1.5
20*40 1,1.5
Packaging & Shipping

 

Packaging & Shipping
Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding


 
Project Reference

 

Project Reference
Customizedodern Louver Roof Pergola Aluminum Lovre Shades for Wall Cladding
If you are interested in our products or have any questions. Please feel free to contact us!

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier